Title: Thermal characteristics of plate-type evaporative condenser
Abstract: Experimental studies on major factors affecting thermal characteristics of the plate-type evaporative condenser,i.e.,air wet-bulb temperature,condensation temperature and relative moisture were conducted.The results showed that condensation temperature and condensation pressure increased with increasing inlet air wet-bulb temperature.Compressor power consumption was greatly affected by inlet air relative humidity and wet-bulb temperature.Comparisons based on the same vapor-compression refrigeration unit showed that the heat flux of the plate-type evaporative condenser was larger by 30.5% than the tube-type evaporative condenser when the condensation temperature was 38℃.The lower the inlet air wet-bulb temperature,the larger the difference between the heat stream density of the plate-type evaporative condenser and the tube-type evaporative condenser at the same condensation temperature.
Publication Year: 2009
Publication Date: 2009-01-01