Abstract: Coagulation with these three agents in the wastewater at pH 11 was more effective for turbidity removal than coagulation with lime. Addition of up to 1.7 lb of clinoptilolite fines per 1000 gallons of wastewater during coagulation did not substantially increase strontium and cesium removal. Filtration without chemical coagulation reduced suspended solids by only 25%. About 70% of the suspended solids remaining in the filtered wastewater were removed in the zeolite column causing plugging which could not be easily dislodged by backwashing. Plugging of the ion exchange columns by previously clarified wastewater required short periods of limited backwashing to relieve the plug. The plugging is due to CaCO/sub 3/ and is not expected to be a severe problem in a full-scale plant with brief detention times between filtration and ion exchange. A high pressure surface wash should be included in the columns to break up crust or plugs at the surface of the zeolite. Centrifugation of iron sludges for 2 min at 2000 g reduced the sludge volume to about 1% of the total wastewater volume. Wet iron sludges from the sludge storage tank were readily dewatered by vacuum filtration. 14 tables, 9 figures.