Title: Extinguishment of compartment fires using portable chemical extinguishers and water
Abstract: Extinguishing experiments on post-flashover room fires, using various kinds of portable extinguihers or water jets, are reported. Typically 2–3 kg of AB-type (general purpose) powders were required to put out test fires of almost 5 MW heat release rate. With water the minimum flow for extinction was 17 l/min or 7.5 g/m2 s. When halon or B-type powder was used the fire re-ignited.
Publication Year: 1986
Publication Date: 1986-12-01
Language: en
Type: article
Indexed In: ['crossref']
Access and Citation
Cited By Count: 8